Here is a full list of advanced settings (parameters) for the ZEN55 Smoke & CO Detector Bridge:
LED Indicator
Parameter 1: Enable or disable the LED indicator to reflect the current on/off status of the connected load (LED on when the load is on, LED off when the load is off).
Values:
0 – LED Indicator disabled;
1 – LED Indicator enabled (default).
Size: 1 byte dec
Relay Alarm Trigger
Parameter 2: Use this parameter to automatically trigger the relay to turn the connected load on when alarm is detected on the input (signal) side.
Values: 0 – auto-trigger disabled; 1 – auto-trigger enabled (default).
Size: 1 byte dec.
Auto Turn-Off Timer
Parameter 3: Use this parameter to set the time after which you want the device connected to the relay to automatically turn off once it has been turned on. The number entered as value corresponds to the number of seconds.
Values: 0 – timer disabled (default); 1 – 4294967295.
Size: 4 byte dec.
Auto Turn-On Timer
Parameter 4: Use this parameter to set the time after which you want the device connected to the relay to automatically turn on once it has been turned off. The number entered as value corresponds to the number of seconds.
Values: 0 – timer disabled (default); 1 – 4294967295.
Size: 4 byte dec.
On / Off Status After Power Failure
Parameter 5: Set the on/off status for the relay after power failure.
Values:
0 – forced to OFF (regardless of state prior to power outage);
1 – forced to ON (regardless of state prior to power outage);
2 – remembers and restores on/off status after power failure (default);
Size: 1 byte dec
Association Reports
Parameter 6: Decide when the device will send BASIC_SET commands to devices associated in Group 2 (Smoke Alarm).
Values:
0 – BASIC_SET (0xFF) ON when smoke is detected, BASIC_SET (0x00) OFF when smoke is not detected (default)
1 – BASIC_SET (0x00) OFF when smoke is detected, BASIC_SET (0xFF) ON when smoke is not detected
2 – BASIC_SET (0xFF) ON when smoke is detected, no commands sent when smoke is not detected
3 – BASIC_SET (0x00) OFF when smoke is detected, no commands sent when smoke is not detected
4 – BASIC_SET (0x00) OFF when smoke is not detected, no commands sent when smoke is detected
5 – BASIC_SET (0xFF) ON when smoke is not detected, no commands sent when smoke is detected
Size: 1 byte dec
Parameter 7: Decide when the device will send BASIC_SET commands to devices associated in Group 3 (CO Alarm).
Values:
0 – BASIC_SET (0xFF) ON when CO is detected, BASIC_SET (0x00) OFF when CO is not detected (default)
1 – BASIC_SET (0x00) OFF when CO is detected, BASIC_SET (0xFF) ON when CO is not detected
2 – BASIC_SET (0xFF) ON when CO is detected, no commands sent when CO is not detected
3 – BASIC_SET (0x00) OFF when CO is detected, no commands sent when CO is not detected
4 – BASIC_SET (0x00) OFF when CO is not detected, no commands sent when CO is detected
5 – BASIC_SET (0xFF) ON when CO is not detected, no commands sent when CO is detected
Size: 1 byte dec
Disable the Sensors or Relay
Parameter 8: After changing this parameter and re-inclusion, the device will show up as a switch, which can be controlled via Z-Wave.
Values:
1 – Enable smoke and CO sensor endpoints and disable the relay switch endpoint (default)
2 – Enable the CO sensor endpoint and disable the smoke sensor and relay endpoints
3 – Enable the smoke sensor endpoint and disable the CO sensor and relay endpoints
4 – Enable the smoke sensor, CO sensor, and the relay endpoints (all endpoints enabled)
5 – Enable the relay and CO sensor endpoints and disable the smoke sensor endpoint
6 – Enable the relay and smoke sensor endpoints and disable the CO sensor endpoint
7 – Enable the relay endpoint and disable the CO sensor and smoke sensor endpoints
Size: 1 byte dec
NOTE: You need to exclude and re-include the device to your hub or re-configure (re-interview) the device if the value of this setting is changed.
Relay Status Reports
Parameter 9: Decide what type of reports the relay part of the device sends back to the hub when it changes status.
Values:
0 – binary switch report for Z-Wave control and input control (from the DC signal sensor)
1 – binary switch report for Z-Wave control and basic report for input control (from the DC signal sensor)
2 – basic report for Z-Wave control and input control (from the DC signal sensor)
Default: 0
Size: 1 byte dec
Supported command classes:
COMMAND_CLASS_ZWAVEPLUS_INFO_V2
COMMAND_CLASS_TRANSPORT_SERVICE_V2
COMMAND_CLASS_SECURITY_2_V1
COMMAND_CLASS_SUPERVISION_V1
COMMAND_CLASS_APPLICATION_STATUS_V1
COMMAND_CLASS_BASIC_V2
COMMAND_CLASS_SWITCH_BINARY_V2
COMMAND_CLASS_NOTIFICATION_V8
COMMAND_CLASS_CONFIGURATION_V4
COMMAND_CLASS_ASSOCIATION_V2
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V3
COMMAND_CLASS_VERSION_V3
COMMAND_CLASS_MANUFACTURER_SPECIFIC_V2
COMMAND_CLASS_DEVICE_RESET_LOCALLY_V1
COMMAND_CLASS_POWERLEVEL_V1
COMMAND_CLASS_FIRMWARE_UPDATE_MD_V5
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3
The ZEN55 Smoke & CO Detector Bridge can be updated via OTA firmware updates, here is how to do that. You can access all firmware files here once you register your product and create an account here. Questions? Just reach out to our support!