You are using an unsupported browser. Please update your browser to the latest version on or before July 31, 2020.
close
You are viewing the article in preview mode. It is not live at the moment.
Looking for Z-Box Hub Support? Please click here to access the Z-Box Hub Support Portal.
Home > Smart Relays > ZEN17 Universal Relay > ZEN17 Universal Relay Advanced Settings
ZEN17 Universal Relay Advanced Settings
print icon

Here is a full list of advanced settings (parameters) for ZEN17 Universal Relay:

Some parameters were added in later firmware updates so please make sure you're on the latest firmware to have all of the settings below available. You can view the change log for the ZEN17 here.

On / Off Status After Power Failure

Parameter 1: Set the on/off status for the relays after power failure.

Values: 

0 – all relays off once restored;

1 – all relays remember and restore status;

2 – all relays on once restored;

3 – R1 remembers and restores status; R2 on;

4 – R2 remembers and restores status; R1 on;

Default: 1. 

Size: 1 byte dec

Input Type for Relay 1 (S1)

Parameter 2: Choose the wall switch or input type you want to connect to the S1 C terminals.

Values:
0 – momentary for lights only;

1 – toggle switch (light on when the switch is toggled up, light off when the switch is toggled down);

2 – toggle switch (state changes whenever the switch is toggled);

3 – garage door momentary mode (for Z-Wave control);

4 – leak alarm (water sensor);

5 – heat alarm;

6 – motion alert;

7 – open/close alert (door sensor)

8 – CO alarm;

9 – CO2 alarm;

10 – on/off report (dry contact switch/sensor);

11 – garage door mode for the relay (momentary contact) and door sensor type for the input (use with wired analog door/window sensors and garage gate openers)
Default: 2.

NOTE: Press and hold the Z-Wave button for 5 seconds (the LED indicator will blink 3 times to confirm the settings change) - parameter 2 will change to value 3 (garage door mode). 
IMPORTANT: If you set this parameter to value 4-11, you’ll need to exclude and re-include the device (without changing any settings) so that a child device is created for the input of your choice!

Size: 1 byte dec

Input Type for Relay 2 (S2)

Parameter 3: Choose the wall switch or input type you want to connect to the S2 C terminals.

Values: 

0 – momentary for lights only;

1 – toggle switch (light on when the switch is toggled up, light off when the switch is toggled down);

2 – toggle switch (state changes whenever the switch is toggled);

3 – garage door momentary mode (for Z-Wave control );

4 – leak alarm (water sensor);

5 – heat alarm;

6 – motion alert;

7 – open/close alert (door sensor);

8 – CO alarm;

9 – CO2 alarm;

10 – on/off report (dry contact switch/sensor);

11 – garage door mode for the relay (momentary contact) and door sensor type for the input (use with wired analog door/window sensors and garage gate openers)
Default: 2.

NOTE: Press, press & hold (so hold on the 2nd click) the Z-Wave button for 5 seconds (the LED indicator will blink 3 times to confirm the settings change) - parameter 3 will change to value 3 (garage door mode). 
IMPORTANT: If you set this parameter to value 4-11, you’ll need to exclude and re-include the device (without changing any settings) so that a child device is created for the input of your choice!

Size: 1 byte dec

LED Indicator

Parameter 5: Choose if you want the LED indicator to turn on when the relays are closed (on) or open (off), or if you want it to remain on or off at all times.

Values: 

0 – LED on when all relays off, LED off when any relay on;

1 – LED on when any relay on, LED off when all relays off;

2 – LED always off;

3 – LED always on;

Default: 0.

Size: 1 byte dec

NOTE: Click the Z-Wave button 5 times quickly to change mode manually.

R1 Auto Turn-Off Timer

Parameter 6: Auto-off timer will automatically turn R1 off after x seconds, minutes, or hours once it has been turned on. Set unit in parameter 15.
Values: 0 – timer disabled (default); 1 – 65535.
Size: 4 byte dec

R1 Auto Turn-On Timer

Parameter 7: Auto-o timer will automatically turn R1 on after x seconds, minutes, or hours once it has been turned off. Set unit in parameter 16.

Values: 0 – Timer disabled 1-65535. Default: 0. 
Size: 4 byte dec

R2 Auto Turn-Off Timer

Parameter 8: Auto-off timer will automatically turn R2 off after x seconds, minutes, or hours once it has been turned on. Set unit in parameter 17.
Values: 0 – timer disabled; 1 – 65535. Default: 0.
Size: 4 byte dec

R2 Auto Turn-On Timer

Parameter 9: Auto-o timer will automatically turn R2 on after x seconds, minutes, or hours once it has been turned off. Set unit in parameter 18.
Values: 0 – timer disabled; 1 – 65535. Default: 0.
Size: 4 byte dec

R1 Input Trigger

Parameter 10: Choose whether the input (switch) on S1 C / VC C triggers the R1 load or just sends input reports for monitoring, keeping output separate.
Values: 0 – input trigger disabled; 1 – input trigger enabled. Default: 1.
Size: 1 byte dec

R2 Input Trigger

Parameter 11: Choose whether the input (switch) on S2 C / VC C triggers the R2 load or just sends input reports for monitoring, keeping output separate.
Values: 0 – input trigger disabled; 1 – input trigger enabled. Default: 1.
Size: 1 byte dec

R1 Auto Turn-Off Timer Unit

Parameter 15: Choose between seconds (1), minutes (0), and hours (2) as the unit for the auto turn-off timer for Relay 1.
Values: 0 – minutes; 1 – seconds; 2 – hours. Default: 0.
Size: 1 byte dec

R1 Auto Turn-On Timer Unit

Parameter 16: Choose between seconds (1), minutes (0), and hours (2) as the unit for the auto turn-on timer for Relay 1.
Values: 0 – minutes; 1 – seconds; 2 – hours. Default: 0.
Size: 1 byte dec.

R2 Auto Turn-Off Timer Unit

Parameter 17: Choose between seconds (1), minutes (0), and hours (2) as the unit for the auto turn-off timer for Relay 2.
Values: 0 – minutes; 1 – seconds; 2 – hours. Default: 0.
Size: 1 byte dec

R2 Auto Turn-On Timer Unit

Parameter 18: Choose between seconds (1), minutes (0), and hours (2) as the unit for the auto turn-on timer for Relay 2.
Values: 0 – minutes; 1 – seconds; 2 – hours. Default: 0.
Size: 1 byte dec

Reversed Reports For S1 Input

Parameter 19: Reverse the reported values for your selected input type on S1 C terminals (select the same value as in parameter 2 to reverse values).

Values:

0 – values reported as normally open, not reversed;

4 – leak alarm (water sensor);

5 – heat alarm;

6 – motion alert;

7 – open/close alert (door sensor);

8 – CO alarm;

9 – CO2 alarm;

10 – on/off report (dry contact switch/sensor);

Default: 0.

NOTE: This will not affect the relay behavior if you leave the input linked to the output, it will still trigger the relay to on when the circuit is closed (if connected between NO-C), regardless of the reported value. This setting only affects the reports displayed in the hub for the input and does not affect the relay (output) behavior.
Size: 1 byte dec

Reversed Reports For S2 Input

Parameter 20: Reverse the reported values for your selected input type on S2 C terminals (select the same value as in parameter 3 to reverse values).

Values:

0 – values reported as normally open, not reversed;

4 – leak alarm (water sensor);

5 – heat alarm;

6 – motion alert;

7 – open/close alert (door sensor);

8 – CO alarm;

9 – CO2 alarm;

10 – on/off report (dry contact switch/sensor);

Default: 0.

NOTE: This will not affect the relay behavior if you leave the input linked to the output, it will still trigger the relay to on when the circuit is closed (if connected between NO-C), regardless of the reported value. This setting only affects the reports displayed in the hub for the input and does not affect the relay (output) behavior.
Size: 1 byte dec

DC Motor Mode

Parameter 24: Sync R1 and R2 together to prevent them from being activated at the same time. Set value to 1 to enable the DC motor mode.
Values:

0 – DC motor mode disabled; 1 – DC motor mode enabled. Default: 0.
Size: 1 byte dec

R1 Input Trigger Duration

Parameter 25: Set trigger duration for input on R1 to make sure the contact made at the input is recorded by the device and the output is triggered and the status is reflected in the hub.

The value of this setting corresponds to the amount of time contact needs to be made for at the input for the status change to be recorded. This is especially useful when using the Universal Relay with doorbells or other buttons that may be pushed for a very short instant or when sensors are connected on the input side and you need to record every single status change even when they occur in less than half a second.
Values: 0-100 (1 = 0.1 second). Default: 5.
Size: 1 byte dec.

R2 Input Trigger Duration

Parameter 26: Set trigger duration for input on R2 to make sure the contact made at the input is recorded by the device and the output is triggered and the status is reflected in the hub. The value of this setting corresponds to the amount of time contact needs to be made for at the input for the status change to be recorded. This is especially useful when using the Universal Relay with doorbells or other buttons that may be pushed for a very short instant or when sensors are connected on the input side and you need to record every single status change even when they occur in less than half a second.
Values: 0-100 (1 = 0.1 second). Default: 5. 
Size: 1 byte dec

Fixed Input Actions

Parameter 27: Set a fixed action to the inputs on your Universal Relay. Enable custom input behavior with dedicated inputs for actions on a selected relay. 

For example, you can connect something to input 1 to only turn relay 1 ON whenever the input changes state and connect something to input 2 to only turn relay 1 OFF whenever the input changes state. This setting is designed for rare and niche scenarios so please do not use it unless your unique situation requires it. NOTE: Expert users only.
Values:

0 – Disabled;

1 – S1 for ON on R1, S2 for OFF on R1;

2 – S1 for ON on R2, S2 for OFF on R2;

3 – S1 for ON on R1 and R2, S2 for OFF on R1 and R2;

Default: 0.
Size: 1 byte dec

Simultaneous On/Off For R1 & R2 (Only available on VER 2.0 800 Series)

Parameter 28: When enabled (1) and when parameter 2 is set to 0-3, S1/C input and hub commands will trigger both R1 & R2 on/off simultaneously. 

With parameter 28 enabled, the S2/C input is automatically separated from the output and can be used independently for monitoring purposes only (when parameter 3 is set to values 4-10 ONLY).
Values: 0 – Disabled; 1 – Enabled. Default: 0.
Size: 1 byte dec.

How to Access the Advanced Settings

How to Access the Advanced Settings for the ZEN17 on Home Assistant

How to Access the Advanced Settings for the ZEN17 on HomeSeer

How to Access the Advanced Settings for the ZEN17 on Hubitat

How to Access the Advanced Settings for the ZEN17 on SmartThings

How to Access the Advanced Settings for the ZEN17 on Z-Box

Manual Control From the Z-Wave Button

3 x tap: enter inclusion (pairing) mode

5 x tap: change LED indicator mode (see parameter 5)

 

The ZEN17 Universal Relay can be updated via OTA firmware updates, here is how to do that. You can access all firmware files here. Questions? Just reach out to our tech support team.

Feedback
2 out of 2 found this helpful

Have you tried our virtual assistant chatbot? This AI tool can help you find answers from thousands of articles in our Knowledge Base quickly. Find it in the bottom righthand corner of the page.

Need more help? Our friendly team is ready to help you with any questions or concerns you may have about Zooz devices. Click here to submit a support ticket.

Are your devices registered? Extended warranty and firmware access is available for registered Zooz customers. Click here to submit your registration form.

Find the latest Zooz devices and great Z-Wave deals at The Smartest House.
 
scroll to top icon